Adaptive Single Ended Protection Scheme for parallel Transmission Lines

Show simple item record

dc.contributor.author Mourad, Dina
dc.contributor.author Shehab Eldin, E. H.
dc.date.accessioned 2019-12-03T08:16:29Z
dc.date.available 2019-12-03T08:16:29Z
dc.date.issued 2017
dc.identifier.citation Cited References in Web of Science Core Collection: 26 en_US
dc.identifier.isbn 978-1-5386-0990-3
dc.identifier.uri https://ieeexplore.ieee.org/abstract/document/8073174
dc.description Accession Number: WOS:000428724000183 en_US
dc.description.abstract This paper presents a novel and adaptive non communication based protection proposal. It, also, provides a proposed transform, which is named the Akrap transform, to extract the transient components. The proposal uses the positive sequence currents and the Akrap transform to protect the double-circuit transmission line. The suggested proposal consists of two steps; while Step 1 detects internal faults, Step 2 identifies the faulted circuit. The proposal uses the three phase currents measurements at one end of the double circuit line. Thus, there is no need to any communication links. The proposal is evaluated with ATP-EMTP versatile simulations. Moreover, it has advantages like its protection to the total line length and the simple and fewer numbers of equations. It does not depend on the impedances of sources, the initial fault conditions as type of fault, inception time of fault, distance of fault, and resistance of fault and the current transformer saturation. en_US
dc.description.sponsorship IEEE Egypt Sect; IEEE Power & Energy Soc, Egypt Chapter; PELS, Egypt Chapter en_US
dc.language.iso en en_US
dc.publisher IEEE en_US
dc.relation.ispartofseries 19th International Middle East Power Systems Conference (MEPCON);Proceedings of the International Middle East Power Systems Conference Pages: 1208-1215
dc.relation.uri https://cutt.ly/Ue3ipxJ
dc.subject University for Single ended protection en_US
dc.subject parallel transmission line en_US
dc.subject protective relaying en_US
dc.subject Adaptive en_US
dc.subject Akrap transform en_US
dc.title Adaptive Single Ended Protection Scheme for parallel Transmission Lines en_US
dc.type Book chapter en_US
dc.Affiliation October University for modern sciences and Arts (MSA)